Fenestration Testing

Accommodate testing up to 80" x 80" windows and doors

Main assmbly v25.png

Structural – Wind Load & Deflection (NAFS, ASTM E330) 

Procedure: Uniform positive and negative air pressure is applied across the specimen. Deflection and permanent damage are measured.

Ratings:

Design Pressure (DP): Measured in Pa (Pascals).

Common residential ranges: +/- 2400 Pa 

Higher-performance: +/- 4800 Pa  or above

Deflection Limit: Typically L/175 (span/175),  L/240 for stricter performance.

Air Leakage – Infiltration/Exfiltration (ASTM E283)

Procedure: Product is sealed into a test chamber, and airflow is measured under pressure differences.

Ratings:

Reported in cfm/ft² of frame area at a specified pressure difference.

NAFS/CSA requirements:

Windows/Doors: ≤ 0.3 cfm/ft² at 75 Pa

Water Penetration – Static Pressure with Spray Rack (ASTM E547 / E1105)

Procedure: Product is subjected to uniform water spray (5.0 US gal/ft²/hr) while air pressure is applied to simulate wind-driven rain.

Ratings:

Pressure difference (Pa) at which no water penetrates beyond the interior face.

Typical test pressures: 150 Pa up to 720 Pa depending on rating class.

Main assmbly 80x80.png